Description
DSPSX000 Product Manual
- Protocol Conversion Feature Converts up to 15 Protocols Simultaneously
- Extensive Built-in Driver List Allows Easy Data Mapping to PLCs, PCs, and SCADA Systems
- 2 RS-232 Serial Ports
- 1 RS-422/485 Serial Port
- 10 Base-T/100 Base-TX Ethernet Connection Can Connect To Multiple Devices Via Up To 10 Protocols Simultaneously
- Independent Serial Ports Provide Virtually Unlimited Integration Methods
- UL Listed for use in Hazardous Locations (See literature for class and division details)
- CompactFlash® Slot Allows Process Data to be Logged Directly to CSV Files
- 320 x 240 Virtual HMI Offers Built-in PC-based SCADA Functionality
- Webserver Provides Worldwide Access To Data Logs And Virtual HMI
- Alarm Notifications can be sent via Email or Text Messages
The DSPSX000 is the single-device solution for protocol conversion. The DSP bridges the communication gap between disparate serial, Ethernet and fieldbus devices—unlocking untold information from PLCs, drives, motion controllers, etc., orphaned by incompatible communications standards. Drag and drop register mapping allows a Siemens PLC to talk to an Allen Bradley drive in just seconds. With a growing list of over 300 serial, Ethernet and fieldbus drivers, the DSP allows you to choose the best-in-class automation components, without worrying over whether or not they’ll communicate with one another.
Getting legacy machines onto a common communications backbone used to be largely impossible, sometimes requiring a complete replacement of the automation components. The DSPSX000 allows you to convert your old PLC’s and drive’s proprietary protocol into a modern and open standard. By unlocking information hidden in these legacy devices, you save money while avoiding a risky upgrade to equipment that is otherwise working perfectly.
The DSPSX000 messaging facilities can be used to send alarms or events using email or SMS text messages to PCs, as well as PDAs and mobile phones. Files can be attached to email so report or logging information arrive directly to the appropriate personnel, facilitating faster intervention or maintenance when problems occur.
Specifications
POWER: 24 VDC ± 10%
200 mA min., without expansion card
1 Amp maximum with expansion card fitted
Must use NEC Class 2 or Limited Power Source (LPS) rated power supply.
COMMUNICATIONS:
USB/PG Port: Adheres to USB specification 1.1. Device only using Type B
connection.
Serial Ports: Format and Baud Rates for each port are individually software
programmable up to 115,200 baud.
RS232/PG Port: RS232 port via RJ12
COMMS Ports: RS422/485 port via RJ45, and RS232 port via RJ12
DH485 TXEN: Transmit enable; open collector, VOH = 15 VDC,
VOL = 0.5 V @ 25 mA max.
Ethernet Port: 10 BASE-T / 100 BASE-TX
RJ45 jack is wired as a NIC (Network Interface Card).
LEDs:
STS – Status LED indicates condition of Data Station.
TX/RX – Transmit/Receive LEDs show serial activity.
Ethernet – Link and activity LEDs.
CF – CompactFlash LED indicates card status and read/write activity
4. MEMORY:
On-board User Memory: 4 Mbytes of non-volatile Flash memory.
On-board SDRAM:
DSPSX: 2 Mbytes
DSPGT: 8 Mbytes
Memory Card: CompactFlash Type II slot for Type I and Type II cards.
REAL-TIME CLOCK: Typical accuracy is less than one minute per month
drift. Crimson 2.0’s SNTP facility allows synchronization with external servers.
Battery: Lithium Coin Cell. Typical lifetime of 10 years at 25 ºC.
A “Battery Low” system variable is available so that the programmer can choose specific action(s) to occur when the battery voltage drops below its nominal voltage.
This unit is NOT field serviceable. All work must be done by a qualified
technician.
ENVIRONMENTAL CONDITIONS:
Operating Temperature Range:
DSPSX000: 0 to 50 °C
Storage Temperature Range: -30 to 70 °C
Operating and Storage Humidity: 80% max relative humidity,
non-condensing, from 0 to 50 °C
Vibration to IEC 68-2-6: Operational 5 to 150 Hz, 2 g.
Shock to IEC 68-2-27: Operational 30 g
Altitude: Up to 2000 meters
CONSTRUCTION: Case body is burgundy high impact plastic and
stainless steel. For indoor use only. Installation Category II, Pollution
Degree 2.
POWER CONNECTION: Removable wire clamp screw terminal block.
Wire Gage Capacity: 24 AWG to 12 AWG
Torque: 4.45 to 5.34 in/lb (0.5 to 0.6 N-m)
MOUNTING: Snaps onto standard DIN style top hat (T) profile mounting
rails according to EN50022 -35 x 7.5 and -35 x 15.
CERTIFICATIONS AND COMPLIANCES:
CE Approved
EN 61326-1 Immunity to Industrial Locations
Emission CISPR 11 Class A
Safety requirements for electrical equipment for measurement, control, and
laboratory use:
EN 61010-1: General Requirements
EN 61010-2-201: Particular Requirements for Control Equipment
RoHS Compliant
UL Listed: File #E302106
UL Hazardous: File #E317425
ABS Certificate #09-HS426719-B-4-PDA
Refer to EMC Installation Guidelines section of the bulletin for additional information.
WEIGHT: 15.1 oz (428 g)